|
|
What's in the
Simulator 7.0 Patch?
PowerWorld Simulator 7.0 Patch addresses problems that were
detected in the program after its release and introduces some new
functionality. These modifications are listed here. The patch was last
modified December 12, 2001. Minor Updates made to this patch are noted
below along with a date and explanation. This patch was first
introduced on December 11, 2000.
If you are ready to download this patch, click
here to go to the patch download page.
File Input/Output
- (December 11, 2000) Reading in a PWB file for which Custom
Filters have been defined was not working properly. This has been
fixed. Note: if you experience this problem, your PWB file is
actually fine, but you will need to download this patch in order
to read in the file.
- (December 19, 2000) Several minor corrections to reading in VAR
devices from GE PSLF format. These included switched shunt devices
and multi-line section line parameters.
- (January 16, 2001) Using a script file to control a switched
shunt was not working. This has been fixed.
- (January 16, 2001) Writing "database friendly" tables
out from the contingency analysis tool created blank entries under
some circumstances. This has been fixed.
- (January 16, 2001) Significant improvements to saving PWB and
PWD files were made so that the time required to save PWB or PWD
files has decreased substantially.
- (March 20, 2001) A minor error in writing the multi-section line
records for PTI RAW files has been corrected.
- (March 28, 2001) A minor error bug existed if you renumbered the
zone's in your case, and then saved the case as a PTI RAW file.
This was corrected.
- (April 13, 2001) GE PSLF *.epc files which contained no
interface records were not being read properly. This has been
fixed.
- (April 25, 2001) Added the ability to write interface records
out to an Excel Spreadsheet in the "NERC Book of Flowgates"
format. Removed Read/Write abilities for the old NERC text file
format.
- (April 25, 2001) Added the ability to read PTI Version 27
format.
- (July 2, 2001) Modified the writing of PTI contingency file
format to truncate contingency labels down to 12 characters.
- (July 2, 2001) Corrected bug in writing column headers out when
using the "Save As HTML" option in a case information
display.
- (November 16, 2001) Corrected bug when writing out a PTI
formatted case. If the case description had exactly 1 line of text
it resulted in a bug.
Power Flow Solution
- (February 26, 2001) A bug in the handling of DC lines in the
power flow was causing power flow convergence to be slow. This has
been corrected.
- (June 21, 2001) Under rare circumstances, a bug in the
coordination of moving tap changing transformers and
phase-shifting transformers together could be encountered. This
would slow power flow convergence. This has been corrected.
User Interface
- (December 19, 2000) Minor changes in toggling the
"Monitor" field on lines, interfaces, and buses in the
Limit Monitoring Settings Dialog.
- (December 19, 2000) When setting to a flat start, all generator
MVAR outputs were begin set to zero. This has been changed so that
only generators that are on Automatic Voltage Regulation (AVR) are
set to 0 MVAR.
- (January 16, 2001) When the line/transformers case information
display is open, switching between Run Mode and Edit Mode might
cause a nuisance access violation. This has been fixed.
- (February 26, 2001) On the TLR/Generation Shift Factors dialog,
users can now specify the transactor to be either a single bus, or
the slack bus. Also, the Injection Group feature on this dialog
was not working properly. The results for an injection group
always reflected the results for transactor with the slack bus.
- (February 26, 2001) On the TLR/Generation Shift Factors dialog
the option to include phase-shifters in the DC calculation was not
working properly. This has been fixed.
- (March 28, 2001) The user is now allowed to delete substations
which contain buses. The buses are then set to be in no
substation.
- (April 20, 2001) The automatic highlighting of fields on the
one-line diagram after they reach a limit was not working
correctly. The field would change color to blue or red upon
hitting a limit, but the color would not be changed back after the
element was not limiting anymore. This has been fixed.
- (June 12, 2001) Modified monitoring of limits to allow the user
to monitor the lower end of a transmission branch for overloads.
- (June 21, 2001) When scaling flowing arrows according to
percentage, sometimes the arrows were scaled incorrectly and the
direction of flows was sometimes reversed. This has been
corrected.
- (November 16, 2001) Fixed bug with the display of voltage fields
on a one-line. This resulting in a "shadowy" appearance
if you were showing voltages in kV, and displaying a contour.
Fault Analysis
- (December 19, 2000) Correct a mistake in converting per-unit
values in the Fault Analysis to amps. The per-unit values were
calculated correctly, but the conversion to amps was missing a
square root of 3.
- (December 19, 2000) Added ability to show amp values in the list
displays in amps.
- (January 7, 2001) An error was corrected with the modeling of
shunts during fault analysis.
- (December 12, 2001) There was a bug with fault calculations
caused by the 30 degree phase shift of Wye-Delta connected
transformers not being properly taken into account. This has been
fixed.
Linear Analysis Techniques: PTDF, LODF, Available Transfer
Capability (ATC)
- (January 3, 2001) An error was occurring when calculating LODF
values after a new transmission line was created. This effected
LODF calculations as well as ATC calculations.
- (January 7, 2001) An error was occurring when calculating ATC
values if branches included in the contingency list were not set
to be monitored. This has been corrected.
- (April 13, 2001) Added two new options on the ATC form for
determining which Transfer Limitations to report. One limits the
number of limitations for a particular element of the power
system. The other limits the report to include limitations below a
certain MW level.
One-line Diagram Editing
- (December 11, 2000) User may now display the drawing grid on the
one-line diagram.
- (December 11, 2000) User is now able to modify the number of
digits and digits to the right of the decimal point on several
selected analogs at once.
- (January 7, 2001) When entering new transmission lines on the
diagram, the default drawing values for color settings were not
being properly used. This has been fixed.
- (March 20, 2001) Pre-defined borders for all of North America
were added.
|