Fault Analysis Example
PowerWorld
Simulator’s Fault Analysis tool calculates the effects of a fault
throughout a system. Faults can be simulated to occur at a bus or in a line, and can be
one of four types:
- Single Line-to-Ground
- Line-to-Line
- 3 Phase Balanced or
- Double Line-to-Ground
You can specify the location on the line for an in-line fault to
occur, and mutual impedance data can be
imported from other PowerWorld cases or in PTI format.
There are four ways to initiate a fault analysis study:
-
Select Tools >> Fault Analysis from the main menu.
-
Click the Fault button
on the Run Mode toolbar.
-
Right
click on a bus and choose Fault… from the local menu to perform a fault analysis at
that bus
-
Right
click on a line and choose Fault… from the local menu to perform a fault analysis at
that point on the line
Any of these actions opens the Fault Analysis dialog. If you
open the dialog by right-clicking on a bus or line, the fault
information on that bus or line will already be filled in. If you
selected the Fault Analysis… option from the Tools menu or
the Fault button, the information about the location of the fault
will need to be specified.
To get you
started using Simulator’s Fault Analysis tool, let’s consider an
example in a simple, lossless three-bus system. You can download the
PowerWorld case and diagram files to try this example yourself:

Suppose we want to calculate
the fault currents (in Amps) on lines 1-2 and 2-3 when a zero-impedance,
double line-to-ground fault occurs 50% along line 1-3. Follow the
following steps:
-
Make
sure Simulator in Run Mode by clicking on the Run Mode button in the
Program toolbar, or selecting File >> Switch to Run Mode from the main
menu.
-
Open the Fault Analysis dialog.

- Enter the fault impedance. Go to the Options tab in the
Fault Analysis dialog, and enter the R and X values at the top.
Since our fault has zero-impedance, we will leave these at their
default of zero.
- Click OK to close the Mutual Impedance Record
dialog.
Note:
- Mutual impedance values can be loaded from PowerWorld
auxiliary files or in PTI format by clicking the Load Data button.
- The data may be saved in PowerWorld auxiliary format by clicking the
Save Data button.
- Return to the Fault Data tab of the Fault Analysis dialog then the
Calculate button in the lower left corner.
- The
results that we are interested in are the currents in lines 1-2 and
2-3. Click on the Lines tab to see this data. Since this is a
lossless system, the From and To currents are equal for each line.
These are the results as displayed at the bottom of the Fault Data
tab:
|