Advanced Work with B3Flat System
This is a team exercise using
PowerWorld Simulator. You will use the simulation cases already
provided with the software. Teams should have two to three students
- Demonstrate that the current operating point satisfies the
cost-minimization condition that the "penalized"
marginal costs are equal. Use the loss sensitivity factors in your
calculation.
- Demonstrate that reallocation of generation from this economic
optimum will increase costs by reallocating generation levels of
the Home Area generators by plus or minus 20MW in 10MW steps.
Graph total cost in the Home Area as a function of the
reallocation levels. Be sure to take the generators in the Home
Area off of economic dispatch control to do the reallocation.
Also, be sure that Area Control Error is zero after each
reallocation.
- Determine whether the system survives the loss of the largest
unit.
Thanks to Dennis Ray of UW-Madison for this problem.
|